Double compression metal cable glands for SWA/AWA armoured, braided, screened and lead-sheathed cables, also with displacement inner seal against cold flow: Ex db / Ex eb / Ex tb, group I, II and III, M12 to M130 and NPT.





The double compression gland provides two separate seals: a flameproof seal on the inner sheath of the cable and an IP and retention seal on the outer sheath, with the armour clamped and earthed between cone and clamping ring. This page covers every version for armoured cable: standard, universal for armour and braid, for offshore cables, for lead sheath and with displacement inner seal, which reduces the effects of sheath cold flow. All are supplied pre-assembled and fit Ex d, Ex e and Ex t enclosures in Zone 1, 2, 21 and 22.
In the Variants and codes section you find every version with sizes and dimensions: filter by version and size and complete the ordering code with material, seals and accessories, just like the manufacturer's code generator. You can request a quote directly from there.