M-LB surge protection barriers – Type 2 and Type 3 for power supply lines

M-LB-1.275.D · M-LB-4.275TNS.D · M-LB-2.255.T3.D · …

M-LB surge protection barriers for power supply lines: Type 2 acc. to EN 61643-11 for single-phase, TN, TN-C, TN-S and TT systems up to 230/400 V, and Type 3 for fine protection, with pluggable modules and fault indication contact.

CE
Description
Technical Specifications
Applications
Download
Datasheets

M-LB surge protection barriers for power supply lines protect cabinets, power supplies and control systems against surges coming from the mains. Type 2 devices (Class II acc. to IEC 61643-11) are available with 1 to 4 poles for single-phase, TN, TN-C, TN-S and TT systems at 120 V or 230/400 V; Type 3 devices provide fine protection downstream, close to the loads, for 24 V AC, 120 V and 230 V.

Each unit is pre-wired and consists of a base and plug-in protection modules, locked in the base and replaceable without tools via release buttons. The status of every protected line is shown in green/red, and a volt-free change-over contact reports faults to the supervisory system. Spare protection modules (.M) can be ordered separately.

Key features

  • Type 2 acc. to EN 61643-11: In 15 … 20 kA, Imax 40 kA (8/20 µs)
  • Voltage protection level Up max. 0.7 … 1.25 kV, reaction time max. 25 ns
  • Type 3: 25 A nominal load current, fine protection close to the load
  • Modules replaceable without tools; Type 2 modules hot-swappable
  • Status indication for every line and change-over contact for fault signalling
  • UL 94 V-0 thermoplastic housing, DIN rail mounting
  • Conforms to the Low Voltage Directive 2014/35/EU

Use the filters in Variants and codes to find the exact part number: where available you will find the official Pepperl+Fuchs datasheet and, for every code, a quote request. For versions not listed, accessories or availability, contact us.

No items found.
# General Product type: Surge protection barrier for power supply lines Brand: Pepperl+Fuchs Series: M-LB Type: Type 2 / Class II and Type 3 / Class III acc. to EN/IEC 61643-11 Protected lines: 1, 2, 3, 4 Systems: single-phase, TN, TN-C, TN-S, TT Supply scope: base + module (.D) or protection module only (.M) # Certifications Conformity: Low Voltage Directive 2014/35/EU, EN 61643-11 M-LB-2.30.T3.D: ATEX II 3G Ex ec IIC T4 Gc, IECEx Ex ec IIC T4 Gc, UL # Electrical Nominal voltage: 24 V AC, 120 V AC, 230 V AC, 230/400 V AC Max. continuous operating voltage Uc: 30 V, 150 V, 255 V, 275 V AC Nominal discharge current In (8/20 µs): 15 … 20 kA (Type 2), 1 … 3 kA (Type 3) Max. surge current Imax (8/20 µs): 40 kA (Type 2), 2 … 5 kA (Type 3) Voltage protection level Up: max. 1.25 kV (Type 2, 230 V) Reaction time: max. 25 ns Short-circuit withstand: 50 kA rms (Type 2), 6 kA rms (Type 3) Mains-side overcurrent protection: max. 125 A gG (Type 2), max. 25 A gL/gG (Type 3) Fault contact: volt-free change-over, 250 V AC / 0.5 A # Mechanical Width: 18 mm per pole (1 TE acc. to DIN 43880), 72 mm for 4 poles Dimensions: 18 x 90 x 72 mm (1 pole) Housing: grey thermoplastic, UL 94 V-0 Mounting: 35 mm DIN rail acc. to EN 60715 Degree of protection: IP20 Ambient temperature: -40 … 80 °C
{"v":1,"colonne":[{"nome":"Lines","valori":["1","2","3","4"]},{"nome":"System","valori":["Single-phase","TN","TN-C","TN-S","TT","Type 3 (fine)"]},{"nome":"Voltage","valori":["24 V AC","120 V AC","120 V AC/240 V AC","230 V AC","230 V AC/400 V AC","–"]},{"nome":"Supplied as","valori":["Base + module","Protection module only","–"]}],"righe":[["M-LB-1.275.D",0,0,3,0],["M-LB-1.150.D",0,0,1,0],["M-LB-2.275TN.D",1,1,3,0],["M-LB-2.150TN.D",1,1,1,0],["M-LB-3.275TNC.D",2,2,4,0],["M-LB-3.150TNC.D",2,2,2,0],["M-LB-4.275TNS.D",3,3,4,0],["M-LB-4.150TNS.D",3,3,2,0],["M-LB-4.275TT.D",3,4,5,0],["M-LB-1.150.M",0,0,5,1],["M-LB-2.255.T3.D",1,5,3,0],["M-LB-2.275TT.D",1,4,5,0],["M-LB-1.275.M",0,0,5,1],["M-LB-2.30.T3.M",0,5,5,1],["M-LB-2.150.T3.M",0,5,5,1],["M-LB-2.255.T3.M",0,5,5,1],["M-LB-2.30.T3.D without CCC",1,5,0,2],["M-LB-2.150.T3.D without CCC",1,5,1,2]],"datasheet":{"base":"https://files.pepperl-fuchs.com/webcat/navi/productInfo/pds/","pn":["235891","235905","235906","235907","235909","235910","235911","235912","235913","235915","263958","70172492","70172493","70172496","70172497","70172498","70201533","70201536"],"apn":[],"noit":["235891","235905","235906","235907","235909","235910","235911","235912","235913","235915","263958","70172492","70172493","70172496","70172497","70172498","70201533","70201536"]},"fonte":"Pepperl+Fuchs price list 2026 / official datasheets"}
No items found.
Oil & Gas
Oil & Gas
Chemical and petrochemical
Chemical and petrochemical
Pharmaceutical
Pharmaceutical
M-LB surge protection barriers – Type 2 and Type 3 for power supply lines