Services
Tools
Products
>
Isolated barriers
>
HiC analogue isolated barriers – H-System for termination boards
Isolated barriers
sicurezza-barriere-isolate
Pepperl+Fuchs

HiC analogue isolated barriers – H-System for termination boards

HiC2025 · HiC2027 · HiC2031 · HiC2081 · HiC2441 · …

H-System HiC intrinsically safe barriers for analogue signals: SMART transmitter power supplies, current drivers, temperature converters and a universal barrier that plug into termination boards, up to SIL 3.

ATEX
IECEx
UL
SIL
CE
Description
Technical Specifications
Applications
Download
Datasheets

Pepperl+Fuchs H-System HiC isolated barriers connect analogue instruments installed in Zone 0, 1 or 2 to the control system in the safe area. The 12.5 mm wide modules plug into HiC termination boards, which provide the 24 V DC supply, field terminals and the DCS connection: cabinet wiring is reduced and a module can be replaced without touching the cables.

The range covers power supplies for 2-wire SMART transmitters (including dual-output signal splitters), current drivers for I/P converters and positioners, temperature converters for thermocouples, RTDs and potentiometers, and the HiC2441 universal barrier, which adapts itself to the channel type of a universal I/O card. HART communication is passed through bi-directionally.

Key features

  • 24 V DC supply via the termination board (bus powered)
  • 0/4 … 20 mA and 0/1 … 5 V signals, output selectable as source, sink or voltage
  • HART transparent; HiC2025 and HiC2027 also support BRAIN
  • HiC2081 converter for TC, RTD, mV and potentiometers, configurable with PACTware
  • Line fault detection (LFD) with LED and fault bus output (model dependent)
  • Field circuits [Ex ia Ga] IIC, [Ex ia Da] IIIC; ATEX, IECEx, cULus
  • Up to SIL 3 acc. to IEC/EN 61508 (HiC2031ES)

Use the filters in Variants and codes to find the exact part number: where available you will find the official Pepperl+Fuchs datasheet and, for every code, a quote request. For versions not listed, accessories or availability, contact us.

Zone 0
Explosive gas atmosphere present continuously or for long periods
Zone 1
Explosive gas atmosphere likely to occur in normal operation
Zone 2
Explosive gas atmosphere unlikely to occur and, if it does, only for a short period
Zone 20
Explosive dust atmosphere present continuously or for long periods
Zone 21
Explosive dust atmosphere likely to occur in normal operation
Zone 22
Explosive dust atmosphere unlikely to occur and, if it does, only for a short period
# General Product type: Intrinsically safe isolated barrier Brand: Pepperl+Fuchs Series: H-System HiC Functions: SMART transmitter power supply, SMART current driver, temperature converter, universal barrier Channels: 1 or 2 Mounting: on HiC termination board Protocols: HART, BRAIN (HiC2025, HiC2027) Accessory: H-CJC-Pt100 for cold junction compensation (HiC2081) # Certifications ATEX: II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I Zone 2 installation: II 3G Ex ec IIC T4 Gc (model dependent) IECEx: [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Other approvals: cULus, FM (model dependent) SIL: SIL 2 / SIL 3 acc. to IEC/EN 61508 (model dependent) # Electrical Supply: 19 … 30 V DC via termination board Signals: 0/4 … 20 mA, 0/1 … 5 V Temperature inputs: thermocouple, RTD, mV, potentiometer (HiC2081) Current driver output: 4 … 20 mA, load 100 … 650 Ω (HiC2031ES) Typical Ex parameters: Uo 25.2 V, Io 100 mA, Po 630 mW Maximum safe voltage Um: 250 V Galvanic isolation: 375 V peak acc. to IEC/EN 60079-11 # Mechanical Dimensions: 12.5 x 106 x 128 mm (W x H x D) Mass: approx. 100 g Degree of protection: IP20 Ambient temperature: -40 … 70 °C
{"v":1,"colonne":[{"nome":"Function","valori":["Resistance Thermometer for Cold Junction Compensation","SMART Current Driver","SMART Transmitter Power Supply","SMART Transmitter Power Supply/SMART Current Driver","SMART Universal Barrier","Temperature Converter"]},{"nome":"Channels","valori":["1","2","–"]},{"nome":"SIL","valori":["No","SIL 2","SIL 3"]}],"righe":[["H-CJC-PT100",0,2,0],["HiC2027",2,0,1],["HiC2027ES",2,0,2],["HiC2441",4,0,1],["HiC2025ES",2,0,2],["HiC2031ES",1,0,2],["HiC2025",2,0,1],["HiC2031",1,0,1],["HiC2025A",2,0,1],["HiC2081",5,0,1],["HiC2422",3,1,1]],"datasheet":{"base":"https://files.pepperl-fuchs.com/webcat/navi/productInfo/pds/","pn":["268784","272951","286744","315318","322429","70101789","70150447","70150448","70150943","70159064","70160157"],"apn":[],"noit":["268784","272951","286744","315318","322429","70101789","70150447","70150448","70150943","70159064","70160157"]},"fonte":"Pepperl+Fuchs price list 2026 / official datasheets"}
No items found.
Oil & Gas
Oil & Gas
Chemical and petrochemical
Chemical and petrochemical
Pharmaceutical