Services
Tools
Products
>
Remote I/O
>
LB/FB Remote I/O Field Units – Pre-assembled remote I/O enclosures
Remote I/O
sicurezza-remote-io
Pepperl+Fuchs

LB/FB Remote I/O Field Units – Pre-assembled remote I/O enclosures

LB9513 · LB9516 · LB9532 · LB9547 · FB9221 · FB9224 · FB92

Pre-assembled field units for LB Remote I/O (Zone 2 or safe area) and FB Remote I/O (Zone 1) systems, in stainless steel or GRP polyester enclosures, supplied as a certified packaged solution with backplanes installed.

ATEX
CE
Description
Technical Specifications
Applications
Download
Datasheets

Pepperl+Fuchs Field Units are field enclosures already fitted with backplanes, terminals and cable ducts for the LB Remote I/O system (installation in Zone 2 or the safe area) and the FB Remote I/O system (Zone 1). They are supplied as a ready-to-use certified solution: only the I/O modules, power supplies and com units need to be inserted.

The LB9547-S70 stainless steel version for MODBUS TCP, for example, holds up to 46 single-width I/O modules, with redundant fieldbus and power connections and an electropolished IP66/NEMA 4X enclosure.

Key features

  • Field units for the LB system (Zone 2 or safe area) and FB system (Zone 1)
  • Stainless steel or polyester (GRP) enclosures
  • Backplanes, cable ducts and grounding rail with shield terminals pre-installed
  • Any I/O module in any slot, mixed I/O types in one unit
  • Versions with fieldbus and power supply redundancy
  • Accessories: 300 cm backplane connection cables

Use the filters in Variants and codes to find the exact part number: where available you will find the official Pepperl+Fuchs datasheet and, for every code, a quote request. For versions not listed, accessories or availability, contact us.

Zone 1
Explosive gas atmosphere likely to occur in normal operation
Zone 2
Explosive gas atmosphere unlikely to occur and, if it does, only for a short period
# General Product type: Remote I/O field unit Brand: Pepperl+Fuchs Series: LB / FB Remote I/O Systems: LB (Zone 2 or safe area), FB (Zone 1) Enclosure: stainless steel or polyester (GRP) Example LB9547-S70: MODBUS TCP, RJ-45 connector (not included), fieldbus and power supply redundancy Installed components (LB9547-S70): backplanes LB9022E, LB9024A # Certifications Installation: Zone 2 or safe area (LB), Zone 1 (FB) Conformity (LB9547-S70): EMC Directive 2014/30/EU # Electrical Rated voltage (LB9547-S70): 24 V DC Maximum safe voltage Um (LB9547-S70): 60 V Power connection (LB9547-S70): screw terminals, max. 10 mm² # Mechanical Slots (LB9547-S70): 2 bus couplers, 6 power supplies, max. 46 single-width or 23 dual-width I/O modules Enclosure (LB9547-S70): electropolished 316L stainless steel, IP66/NEMA 4X, rain channel, one-piece seal Backplane cable FB9274-300: 12-pin, grey, 300 cm, 530 g
{"v":1,"colonne":[{"nome":"System","valori":["FB (Zone 1)","LB (Zone 2)"]},{"nome":"Enclosure","valori":["Polyester (GRP)","Stainless steel"]}],"righe":[["LB9547-S70-B-MA0-00-0",1,1],["LB9513-PF0-B-0A0-00-0",1,0],["LB9516-PF0-B-0A0-00-0",1,0],["LB9532-T60-B-0A0-00-0",1,1],["LB9547-T70-B-0A0-00-0",1,1],["FB9221-PF0-A-0A0-00-0",0,0],["FB9224-PF0-A-0A0-00-0",0,0],["FB92MU-PF0-A-0A0-00-0",0,0],["FB92EU-PF0-A-0A0-00-0",0,0]],"accessori":[["FB9274-300","Backplane Connection Cable"],["FB9283-300","Connector / accessory"],["FB9272-300","Backplane Connection Cable"]],"datasheet":{"base":"https://files.pepperl-fuchs.com/webcat/navi/productInfo/pds/","pn":["223630","","","","","","","",""],"apn":["238130","","540916"],"noit":["223630","238130","540916"]},"fonte":"Pepperl+Fuchs price list 2026 / official datasheets"}
No items found.
Oil & Gas
Oil & Gas
Chemical and petrochemical
Chemical and petrochemical
Pharmaceutical
Pharmaceutical