Product type: LED exit signs and emergency light for hazardous locations
Power supply: 120/277 VAC dual primary, 60 Hz
Power: CXC and CXD signs 3 W · CMD emergency light 42 W (two 18 W heads)
Colour temperature: 3000 K (CMD emergency light)
Legend: Red EXIT, edge-lit (CXC and CXD signs)
Emergency: Maintenance-free NiCad battery (CMD also lead-calcium); autonomy 180 min (CXC, CXD) or 90 min (CMD), 24 h recharge
Functions: Self-diagnostics, brownout protection, low-voltage battery disconnect
Classification: CXC: Class I Div 1, Groups C, D · Class II Div 1, Groups E, F, G · Class III · Class I Zone 1, Groups IIA, IIB · Zone 2, Groups IIA, IIB + H2, IIC — CXD: Class I Div 2, Groups A, B, C, D · Class II Div 2, Groups F, G · Class III — CMD: Class I Div 2, Groups A, B, C, D · Class I Zone 2, IIA, IIB, IIC
Temperature class: T6 (85 °C) for CXC and CXD · T2B (Div 2) and T1/T2 (Zone 2) for CMD
Certifications: NEC hazardous location classification (Class/Division and Class I Zone); Buy American Act compliant (signs) and ARRA (CMD)
Market: North America (UL/CSA)
Ambient temperature: CXC +10 °C to +50 °C (+50 °F … +122 °F) · CXD +10 °C to +55 °C (+50 °F … +131 °F) · CMD +10 °C to +40 °C (+50 °F … +104 °F)
Ingress protection: IP65, suitable for wet and damp locations (CXC, CXD) · NEMA 4X (CMD)
Body: Copper-free die-cast aluminium alloy with acrylic panels (CXC, CXD) · fibreglass with stainless steel mounting feet (CMD)
Mounting: Wall or pendant with 1/2" NPT hubs (CXC, CXD) · wall with four stainless steel feet (CMD)
Cable entries: 1/2" NPT hubs (CXC, CXD) · conduit entry on 5 sides (CMD)
Finish: Grey
Weight: CXC 6.8 kg (15 lb) · CXD 6.4 kg (14 lb) · CMD 4.5 kg (10 lb)
Warranty: 5 years (CXC, CXD signs) · 3 years (CMD)
{"v":1,"colonne":[{"nome":"Type","valori":["Exit sign","Emergency light"]},{"nome":"Classification","valori":["Class I Div 1","Class I Div 2"]},{"nome":"Faces","valori":["Single","Double","—"]},{"nome":"Duration","valori":["90 min","180 min"]}],"righe":[["CXC-S-F-R-PW-SD",0,0,0,1,0],["CXD-S-F-R-PW-SD",0,1,0,1,0],["CXD-D-F-R-PW-SD",0,1,1,1,0],["CMD-12N-42-18-2-SD",1,1,2,0,0]],"accessori":[],"opzioni":[["Battery","CMD emergency light: lead-calcium battery as an alternative to 12 V NiCad (on request)"],["Mounting","Wall-mounted or suspended signs via 1/2\" NPT hubs"]],"sprite":{"url":"https://cdn.prod.website-files.com/6aa55eca30c5bd4a1e486a4c/6ad61d7aa1426ae4f96abe74_dialight-emergency-exit-classified-sprite.jpg","colonne":2,"lato":200}}