Zone 1
Explosive gas atmosphere likely to occur in normal operation
Zone 2
Explosive gas atmosphere unlikely to occur and, if it does, only for a short period
Zone 21
Explosive dust atmosphere likely to occur in normal operation
Zone 22
Explosive dust atmosphere unlikely to occur and, if it does, only for a short period
Product type: Fixed LED luminaire for hazardous areas, weather-resistant version
Versions: Nordic 1LED WS · Nordic 2LED WS (two independent LED units)
Ex marking: II 2G Ex e mb op is IIC T4 Gb · II 2D Ex tb op is IIIC T90°C Db
Certification: ATEX
Luminous flux: 1595 lm (1LED) · 3140 lm (2LED) measured; 2825 / 5650 lm at source
Power: < 25 W (1LED) · < 50 W (2LED)
Power supply: 110 V AC/DC or 230 V AC ±6%, 50/60 Hz
Colour temperature: 4600-5700 K
Ingress protection: IP66
Ambient temperature: -40 °C to +40 °C
Dimensions and weight: 1LED 535×115 mm, 1.8 kg · 2LED 1020×115 mm, 3.4 kg
{"v":1,"marca":"Atexor","colonne":[{"nome":"Model","valori":["1LED WS (1595 lm)","2LED WS (3140 lm)"]}],"righe":[["SF1LED",0,0],["SF2LED",1,1]],"accessori":[["70908","AISI316 stainless steel pole mounting kit, for Ø 30-45 mm poles",2],["70908_1","Pole mounting kit with pole above the bracket, AISI316, Ø 30-45 mm",2],["Kit staffe palo","Pair of stainless steel brackets for Ø 40-46 mm poles and pipes",3],["70905","AISI316 Low ceiling/wall brackets (pair)",4],["70918","AISI316 High ceiling/wall brackets (pair)",5],["Pellicola protettiva","Replaceable conductive protective film, set of 10 sheets",6]],"opzioni":[["Power supply","110 V AC/DC or 230 V AC ±6%, 50/60 Hz: to be specified when ordering"],["Code","Atexor base code, to be completed and confirmed in the quotation"]],"sprite":{"url":"https://cdn.prod.website-files.com/6aa55eca30c5bd4a1e486a4c/6ad617c3bff2067c826403b2_atexor-nordic-sprite.jpg","colonne":5,"lato":200}}