Zone 1
Explosive gas atmosphere likely to occur in normal operation
Zone 2
Explosive gas atmosphere unlikely to occur and, if it does, only for a short period
Zone 21
Explosive dust atmosphere likely to occur in normal operation
Zone 22
Explosive dust atmosphere unlikely to occur and, if it does, only for a short period
Product type: Cable reels and extension cables for temporary power supply in hazardous areas
Versions: SR16EX 1C (1 socket) · SR16EX 2C (2 sockets) · SEC16EX extension cable
Ex marking cable reels: II 2G Ex e d IIC T4 Gb · II 2D Ex tb IIIC T120°C Db
Ex marking extension cables: II 2G Ex de IIC T4 Gb · II 2D Ex tb IIIC T120°C Db
Certificates: ATEX VTT 09 ATEX 051X (cable reels) · ATEX VTT 11 ATEX 004X (extension cables)
Voltage: 12, 24, 42, 110 V AC/DC or 230 V AC
Maximum current: 16 A
Cable length: small reel 15-50 m, large reel 50-80 m · extension cables up to 25 m
Ingress protection: IP66
Ambient temperature: -20 °C to +55 °C
Cable reel dimensions: small 460 × 550 × 275 mm (23.5 kg with 30 m) · large 580 × 720 × 325 mm
{"v":1,"marca":"Atexor","colonne":[{"nome":"Product","valori":["Reel 16EX cable reel","16EX extension cable"]},{"nome":"Sockets","valori":["1 Ex socket","2 Ex sockets"]}],"righe":[["SR16EX-1C",0,0,0],["SR16EX-2C",0,1,0],["SEC16EX",1,0,1]],"opzioni":[["Voltage","12, 24, 42, 110 V AC/DC or 230 V AC"],["Cable length","Small reel 15-50 m, large reel 50-80 m; extension cables up to 25 m"],["Cable","Orange PUR (H07BQ-F), braided yellow PUR or black rubber"],["Sockets and plugs","CEAG, ATX, Stahl or Marechal"],["Code","Length, cable and sockets complete the code, to be confirmed in the quotation"]],"sprite":{"url":"https://cdn.prod.website-files.com/6aa55eca30c5bd4a1e486a4c/6ad6177a6f2b854e2a1aa33e_atexor-cavi-sprite.jpg","colonne":5,"lato":200}}